TeSys GV auxiliary contact block, for motor circuit breakers GV2 and GV3. 1NO+1NC instantaneous auxiliary contacts. Rated for operation up to 2A/240V AC and 1A/60V DC. To be installed on front side of the circuit breaker, connection by screw clamp terminals. Sold in lots of 10 units. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHS/REACh).
Specifications
Main
Range |
TeSys
TeSys Deca |
Device short name |
GVAE |
Product or component type |
Auxiliary contact block |
Product compatibility |
GV2P
GV2RT
GV2ME
GV3L
GV2LE
GV3P
GV2L |
Mounting location |
Front side |
Pole contact composition |
1 NO + 1 NC |
Quantity per set |
Set of 10 |
Complementary
[Ui] rated insulation voltage |
300 V conforming to UL 508
300 V conforming to CSA C22.2 No 14
250 V conforming to IEC 60947-1 |
[Ue] rated operational voltage |
24…240 V AC
24…60 V DC |
[Ith] conventional free air thermal current |
2.5 A |
Mechanical durability |
100000 cycles |
Minimum switching current |
5 mA |
Minimum switching voltage |
17 V |
Protection type |
GG fuse 10 A
GB2CB06 circuit breaker 10 A |
Rated operational power in VA |
120 VA at 110?120 V AC-15 – electrical durability: 100000 cycles
120 VA at 230?240 V AC-15 – electrical durability: 100000 cycles
48 VA at 24 V AC-15 – electrical durability: 100000 cycles
60 VA at 48 V AC-15 – electrical durability: 100000 cycles |
Rated operational power in W |
15 W at 48 V DC-13 – electrical durability: 100000 cycles
24 W at 24 V DC-13 – electrical durability: 100000 cycles
9 W at 60 V DC-13 – electrical durability: 100000 cycles |
Tightening torque |
1.4 N.m – on screw clamp terminals |
height |
11 mm |
Width |
45 mm |
Depth |
29 mm |
Net weight |
0.02 kg |
Environment
Environmental characteristic |
Normal environment |
Product certifications |
UKCA |
Reviews