TeSys GV auxiliary contact block, for motor circuit breakers GV2 and GV3. 1NO fault signaling contact + 1NC instantaneous auxiliary contact. Instantaneous auxiliary contact rated for operation up to 6A/690V AC and 6A/240V DC. Fault signaling contact rated for operation up to 2A/240V AC and 1A/60V DC. To be installed on left-hand side of the circuit breaker (1 block mounting maximum), connection by screw clamp terminals. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHS/REACh).
Specifications
Main
Range |
TeSys
TeSys Deca |
Device short name |
GVAD |
Product or component type |
Auxiliary contact block |
Product compatibility |
GV2P
GV2LE
GV3L
GV2ME
GV2RT
GV3P
GV2L |
Mounting location |
Left side |
Auxiliary contacts operation |
Fault signal 1 NO |
Pole contact composition |
1 NO + 1 NC |
Complementary
[Ui] rated insulation voltage |
690 V conforming to IEC 60947-1
300 V conforming to UL 508
300 V conforming to CSA C22.2 No 14 |
[Ue] rated operational voltage |
48…690 V AC
24…240 V DC |
[Ith] conventional free air thermal current |
6 A
2.5 A for fault signalling |
Mechanical durability |
100000 cycles |
Minimum switching current |
5 mA |
Minimum switching voltage |
17 V |
Protection type |
GB2CB… circuit breaker
GG fuse 10 A |
Rated operational power in VA |
300 VA at 48 V AC-15 – electrical durability: 100000 cycles
414 VA at 690 V AC-15 – electrical durability: 100000 cycles
500 VA at 110?127 V AC-15 – electrical durability: 100000 cycles
500 VA at 500 V AC-15 – electrical durability: 100000 cycles
650 VA at 440 V AC-15 – electrical durability: 100000 cycles
720 VA at 230?240 V AC-15 – electrical durability: 100000 cycles
850 VA at 380?415 V AC-15 – electrical durability: 100000 cycles
36 VA at 24 V AC-14 – electrical durability: 1000 cycles
48 VA at 48 V AC-14 – electrical durability: 1000 cycles
72 VA at 110?127 V AC-14 – electrical durability: 1000 cycles |
Rated operational power in W |
120 W at 240 V DC-13 – electrical durability: 100000 cycles
140 W at 110 V DC-13 – electrical durability: 100000 cycles
140 W at 24 V DC-13 – electrical durability: 100000 cycles
180 W at 60 V DC-13 – electrical durability: 100000 cycles
240 W at 48 V DC-13 – electrical durability: 100000 cycles
15 W at 48 V DC-13 – electrical durability: 1000 cycles
24 W at 24 V DC-13 – electrical durability: 1000 cycles
9 W at 60 V DC-13 – electrical durability: 1000 cycles |
Tightening torque |
1.4 N.m – on screw clamp terminals |
height |
89 mm |
Width |
9.3 mm |
Depth |
66 mm |
Net weight |
0.055 kg |
Colour |
Dark grey |
Environment
Environmental characteristic |
Normal environment |
Product certifications |
UKCA |
Reviews