GZ1 E are 3 poles 3d thermal-magnetic circuit breakers specifically designed for the control and protectin of motors conforming to standards IEC 60947-2 and IEC 60947-4-1. Setting range of thermal trips is 2.5-4A with thermomagnetic trip unit. It provides IP 41 in GV2 MC01 enclosure and IP 55 in GV2 MC02 enclosure protection. It procures standard reliability and durability with 0.1 Mcycles electrical/mechanical durability. These circuit breakers are designed for connection by screw clamp terminals. Available worldwide, it is multi-standards certified (IEC, UL, CSA, CCC, EAC, Marine) and Green Premium compliant (RoHs/Reach).
Range | Easy TeSys |
---|---|
Range of product | Easy TeSys Power |
product or component type | Circuit breaker |
Device short name | GZ1E |
Device application | Motor |
Trip unit technology | Thermal-magnetic |
Suitability for isolation | Yes conforming to IEC 60947-1 appendix 7.1.6 |
Colour | Grey (RAL 7011) |
poles description | 3P |
---|---|
Network type | AC |
Utilisation category | AC-3 |
Network frequency | 50/60 Hz conforming to IEC 60947-2 |
mounting mode | By clips By screws |
mounting support | Rail |
Mounting position | Any position |
Motor power kW | 0.75 kW at 230 V AC 50/60 Hz 1.5 kW at 400 V AC 50/60 Hz 1.5 kW at 440 V AC 50/60 Hz 2.2 kW at 500 V AC 50/60 Hz 3 kW at 690 V AC 50/60 Hz |
Breaking capacity | Icu: >= 100 kA at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 Icu: >= 100 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 Icu: >= 100 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 Icu: >= 100 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 Icu: 2 kA at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
[Ics] rated service short-circuit breaking capacity | 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
Control type | Push-button |
Thermal protection adjustment range | 2.5…4 A |
Magnetic tripping current | 51 A |
[Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
[Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
[Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
Power dissipation | 2.5 W (per pole) |
Mechanical durability | 100000 cycles |
Electrical durability | 100000 cycles for AC-3 |
Maximum operating rate | 25 cyc/h |
Connections – terminals | Screw clamp terminals 2 1…6 mm² – cable stiffness: solid Screw clamp terminals 2 1.5…6 mm² – cable stiffness: flexible without cable end Screw clamp terminals 2 1…4 mm² – cable stiffness: flexible with cable end |
Height | 89 mm |
Width | 44.5 mm |
Depth | 78 mm |
net weight | 0.26 kg |
Standards | IEC 60947-4 IEC 60947-2 |
---|---|
Protective treatment | TH |
IP degree of protection | IP20 conforming to IEC 60529 |
Ambient air temperature for operation | -20…60 °C |
ambient air temperature for storage | -40…80 °C |
Fire resistance | 960 °C conforming to IEC 60695-2-1 |
Operating altitude | 2000 m |